SD119-2L
HONEYWELL SENTEK -2 Wire Photoelectric Smoke Alarm with Remote LED Output มีไฟ Led รีโมท ระบบไฟอลาม
CONVENTIONAL PHOTOELECTRIC SMOKE AND HEAT ALARM
All of the Sentek’s SD-119 series detectors meet the requirements of UL 268 and EN 54-7/5 for use in fire alarm signaling systems. They are intended for use in 2-wire/4-wire Class A or B supervised zone circuits. The SD-119 series detectors are subject to panel compatibility limits and compliance with corresponding NFPA 72E standards, local codes, and ordinances.
The SD-119 series include 2-wire and 4-wire detectors, which provide fast and reliable response for photoelectric smoke and heat (135o F) detection. While the smoke and heat detection circuits operate independently, their outputs being “OR’ connected, The SENTEK SD-119 series detectors provide the fire detection performance by acting as a smoke sensor and/or a 135o F heat detector at the same location.
PRODUCT FEATHERS
• 2 or 4 wire models
• Advanced detection and discrimination algorithms
• Easy installation and maintenance
• Sleek low-profile housing design
• Durable sensor head, no need for replacement
• SMD circuit board design-satisfactory quality and reliability guaranteed
• Integrated heat detector for SD-119-2H and SD-119-4H models
• N/C (normal/close)-N/O (normal/open)selectable relay output
• AR (Auto Reset) function for security systems (optional for 4 wire models) Sensor base option: standard and Shottky Diode
• Five-year limited warranty
The range includes:
SD-119- 2 2 wire photoelectric smoke alarm
SD-119- 2- LED 2 wire photoelectric smoke alarm with remote LED output
SD-119-2H 2 wire photoelectric smoke and heat alarm
SD-119- 2H-LED 2 wire photoelectric smoke and heat alarm with remote LED output
SD-119- 4 4 wire photoelectric smoke alarm (12/24VDC)
SD-119- 4B 4 wire photoelectric smoke alarm with Buzzer (12/24VDC)
SD-119- 4AR 4 wire photoelectric smoke alarm with auto-reset function (12/24VDC)
SD-119- 4ARB 4 wire photoelectric smoke alarm with auto-reset function and Buzzer (12/24VDC)
SD-119- 4H 4 wire photoelectric smoke and heat alarm (12/24VDC)
SD-119- 4HB 4 wire photoelectric smoke and heat alarm with Buzzer (12/24VDC)
SD-119- 4HAR 4 wire photoelectric smoke and heat alarm with auto-reset function (12/24VDC)
2 Wire SD-119 Series | SD119-2 | SD119-2L | SD119-2H | SD119-2HL |
Thermal | – | 57°C | ||
Voltage DC | 10.8~33V | |||
Standby Current (Max.) | 80μA | |||
Alarm Current 12/24V | 22/55mA | |||
Surge Current (Max.) | 160μA | |||
Star-Up Time (Max.) | 30S | |||
Permissible Current (Max.) | 80mA | |||
Frequency | 1~3 Seconds | |||
Alarm contact | – | |||
Base model | P/N852001 | P/N854001 | P/N852001 | P/N854001 |
- Smoke Sensitivity: 2.26+/-1.21%/FT Obscuration (UL standard)
- Ceiling Spacing: 50 foot rating for heat sensor
- Reset Voltage: less than 1 volt
- Reset Time: less than 1 second
- Alarm Indicator: LED continuously emitting red light
- Remote Output: 25 mA max., diode gate
- Temperature Range: -10°C to 50°C
- Permissible Current: 80mA maximum
- Humidity: 0 to 95% RH, no condensation or icing
- Alarm Contact: (for 4-wire) NO or NC Operation, Form A: 1.0A@30VDC/0.5A@125VAC
- Dimensions: 100mm (dia) x 46mm (ht) with base Weight: 130g/set with base