อุปกรณ์โมดูลตรวจสอบแบบสองสาย สำหรับสัญญาณเตือนอัคคีภัยแบบสัมผัส Honeywell Morley

The HM-DMMI-UL Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally open, contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator.

HM-DMMI-UL Applications: Monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally open, drycontact alarm activation devices. Use it to monitor normally-open supervisory devices with special supervisory indication at the control panel. The monitored circuit may be wired as an NFPA (Class B) Initiating Device Circuit. A 47K Ohm end of line resistor (provided) terminates the Class B circuit.

HM-DMMI-UL Operation: Each HM-DMMI-UL uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of
its Initiating Device Circuit (IDC). A flashing LED indicates that the module communicates with the control panel. The LED steadily illuminates when an alarm starts (subject to current loop limitations).

  • Built-in type identification automatically identifies this device as a monitor module to the control panel
  • Powered directly by two-wire SLC loop. No additional power required
  • High noise (EMF/RFI) immunity
  • SEMS screws with clamping plates for easy wiring
  • Direct-dial entry of address: 61-99 for models SMX and STX
  • LED flashes during normal operation and steadily illuminates to indicate alarm

HM-DMMI-UL TECHNICAL SPECIFICATIONS

Nominal Operating Voltage15 to 32 VDC
Maximum SLC current draw5.0 mA (LED on)
Maximum IDC wiring resistance375 μA (LED flashing), 1 communication every 5 seconds, 47k EOL
Maximum IDC wiring resistance1500 Ohms
Maximum IDC Voltage11 V
EOL resistance47K Ohms
Temperature range32°F to 120°F (0°C to 49°C)
Humidity range10% to 93% non-condensing
Dimensions4.5″ (11.43 cm) high x 4″ (10.16 cm) wide x 1.25″ (3.175 cm) deep. Mounts to a 4″ (10.16 cm) square x 2.125″ (5.398 cm) deep boxS
SYS/HS

Standard: UL

  • It is possible to set the display light to high or low, the volume setting for 3 levels of continuous and temporary.
  • Luxurious design with high aesthetics, compact and easy to install.
  • Automatically synchronize alarm flash light for 30 minutes.
  • Flash mode after 1 second

FEATURES

  • Operating temperature: 0-49 degrees Celsius
  • Humidity: 10-93% RH, No dew condensation.
  • Operating voltage: 16-33 VDC (normally at 24V)
  • Sound intensity: ≥82dBA.
SYS/ST

Horn-Strobe Light Red

Honeywell’s SYS/ST strobe features a red housing and universal fire symbol to meet virtually any application requirement. A mounting plate allows the device to be compatible with a wide range of backbox sizes. Its settings are done using easy-to-set rotary switches on the back of the device while synchronization is achieved without the use of additional modules. When powered with a filtered DC source, it is capable of self synchronization for 30 minutes per NFPA72.

HM/MM3E/UL

HM-MM3E-UL is a miniature monitor module – 1.3” (3.302 cm) H x 2.75” (6.985 cm) W x 0.65” (1.651 cm)
D – that supervises Class B circuit of dry-contact input devices. Thanks to its compact design, the HM-MM3E-UL can be mounted in a single-gang box behind the device it monitors.

HM-MM3E-UL Operation: Each HM-MM3E-UL uses one of the available module addresses on an SLC loop. It responds to regular polls
from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC).

  • Powered directly by two-wire SLC loop No additional power required
  • High noise (EMF/RFI) immunity
  • Tinned, stripped leads for easy wiring
  • Direct-dial entry of address: 61-99 for models SMX and STX

HM/MCP/GLASS/UL

The HM-MCP-GLASS-ULis an addressable manual break glass call point which, as a simple rotary decade, switch at the rear of the unit for addressing.

A specialist test key may be inserted into the bottom of the unit to lower the glass and release the micro-switch – enabling a complete functionality test.

The HM-MCP-GLASS- UL call point is designed to provide a manual alarm interface to Morley IAS’s fire alarm control panel.

Installation efficiency and compliance with the latest standards are at the heart of the call point range.

  • Innovative “Plug and Play” installation concept
  • Analogue addressable communications
  • Integral LED

HM/DISO/UL

The HM-DISO-UL Fault Isolator Module is used with the fire alarm control panels (FACPs) to protect the system against wire-to-wire short circuits on the SLC loop. The HM-DISO-UL should be placed between each
device on the SLC loop to isolate a short circuit problem between the modules. It is required for true Style 7 operation, so that other devices can continue to operate normally in the event of a short circuit on the SLC.

  • Powered by SLC loop directly, no external power required
  • Mounts in standard junction boxes (4.0”/10.16 cm square, 2.125”/5.398 cm deep)
  • Integral LED blinks to indicate normal condition and illuminates steady when short circuit condition is detected
  • High noise (EMF/RFI) immunity

HM/DCZRM/UL

HM-DCZRM-UL is a standard-sized module used to monitor and supervise compatible two-wire,
24-Volt, smoke on a Class B circuit.

The HM-DCZRM-UL Interface Module is intended for use in intelligent, addressable systems, where the
individual address of each module is selected using built-in rotary switches. This module allows intelligent
panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module.

  • Supports compatible two-wire smoke detectors
  • Supervises IDC wiring and connection of external power source
  • High noise (EMF/RFI) immunity
  • SEMS screws with clamping plates for ease of wiring
  • Direct-dial entry of address: 61 -99 for models SMX and STX
  • LED flashes during normal operation
  • LED steadily illuminates to indicate an alarm on command from the control panel

HM/D240CMO/UL

The HM-D240CMO-UL Addressable Relay Module provides the system with a dry contact output for activating a variety of auxilary devices, such as fans, door holders, dampers, control equipment, etc. Addressability allows the dry contact to be activated through panel programming, on a select basis.

  • Built-in type identification automatically identifies these devices to the control panel
  • Internal circuitry and relay powered directly by two-wire SLC loop
  • Integral LED “blinks” green each time a communication is received from the control panel and turns
    on in steady red when activated
  • High noise immunity (EMF/RFI)
  • Wide viewing angle of LED
  • SEMS screws with clamping plates for wiring ease
  • Direct-dial entry of address: 61 -99 for models SMX and STX

HM/DCMO/UL

The HM-DCMO-UL Addressable Control Module provides a circuit for Notification appliances like horns, strobes, and more. Addressability allows the HM-DCMO-UL to be activated through panel programming, on a select (zone or area of coverage) basis.

  • Built-in type identification automatically matches devices to the control panel
  • Internal circuitry powered directly by a two-wire SLC loop The HM-DCMO-UL module requires power (for horns, strobes, etc.)
  • Integral green LED blinks each time a communication is received from the control panel and turns on steady red when activated
  • High noise immunity (EMF/RFI)
  • The HM-DCMO-UL may be used to switch 24-volt NAC power
  • Wide viewing angle of LED
  • SEMS screws with clamping plates for easy wiring
  • Direct-dial entry of address: 61 -99 for models SMX and STX