Search for:
MI-MM3E-S2
MI-MM3E-S2
EUROPEAN MINI-MOD MORLEY
MI-MM3E-S2

The MI-MM3E-S2 is an addressable input module. It will interface with contact devices such as security contacts, waterflow switches and call points.

It is capable of being connected in Class B wiring configurations.

It provides a two-wire initiating circuit for normally open contact fire alarm and security devices.

In addition to transmitting the supervised state of the monitored device (normal, open or short), the full analog supervision measurement is sent back to the panel.

The compact size allows it to fit inside devices or juntion boxes behind devices.

Its size and light weight allows it to be installed without the need to be rigidly mounted.

All Morley-IAS products are covered by our extended 3 year warranty.

FEATURES
  • Compact size
  • Rotary address switches
  • Low standby current
  • Complies with EN54-18

MI/PTSE/S2/IV
PHOTO THERMAL DET, ADV PROTOCAL,MOR, IN
MI/PTSE/S2/IV

S200A incorporates major hardware and software technology driven developments. A completely new optical chamber design is proven in extensive testing to be more efficient, less liable to is proven in extensive testing to be more efficient, less liable to false alarm due to dust and insects and less susceptible to fault in high air velocities or back pressure. Extensive hydrodynamic modelling has confirmed the greater efficiency of the new chamber and housing shape combination. Large-scale integration of the all-new electronics, through the fully automated surface mount PCB assembly, coupled with in-line testing through the manufacturing process, laser PCB cutting along with a completely new compound of plastic offers
i.mproved quality and reliability

All S200A detectors are environmentally friendly and meet the WEEE and RoHS legislative requirements, minimising end of life disposal costs, and are mechanically and electrically backwards c. ompatible with existing devices.

FEATURES
  • Available with or without short circuit isolation
  • Isolator per device allowsfaster, more precise fault finding
  • Rotary decade address switches
  • Ivory colour to harmonise with the modern built environment
  • 100% mechanical and electrical backwards compatibility
  • New base design to complement the detector and ease installation and wiring

MI/DMMI
MI/DMMI
INPUT MODULE SINGLE, MIAS, IN
MI/DMMI /MI-DMM2I

The MI-DMMI and MI-DMM2I monitor modules are used with the Morley-IAS intelligent fire alarm control panels to provide a single or dual input circuit from external devices.

Each input is continuously monitored for normal, open circuit and alarm conditions. Changes to the status of
the input circuits are communicated to the panel where the appropriate actions may be undertaken.

The MI-DMMI requires a single address and the MI-DMM2I two addresses of the ninety-nine possible module addresses available on a loop. It responds to regular polling from the control panel indicated by a pulsing LED every successful communication.
The MI-DMMI and MI-DMM2I use a unique mechanical design allowing each module to be mounted either in a wall box (M200E-SMB) or on a DIN rail (using M200E-DIN). Irrespective of the mounting method chosen, the address switch is both visible and accessible for selection. To help engineers in the maintenance and fault finding process, both the LEDs and the address switches can be viewed without having to remove the
cover of the mounting box. The LEDs, being multi colour, provide diagnostic information regarding
the status of the output. For ease of installation, testing and maintenance, the field wiring terminals are of a plug in design

FEATURES
  • Single or dual inputs
  • DIN rail mounting option
  • Surface mounting option
  • Tri-colour LED status indication
  • Built-in short circuit isolators
  • Visible address selector switches
  • LED status visible in 2 planes
  • Plug in connectors
  • Approved to GEA GEI 1-082 and CEA GEI 1-084

MI/MCP/FLEX
ADD.MCP,MIAS,FLEXI,INEADER
MI/MCP/FLEX

The MI-MCP Series Manual Call Points are designed to provide a manual alarm interface to Morley IAS’s fire alarm control panel. Installation efficiency, flexibility and compliance with the latest standards are at the heart of the call point range.

The unique ‘plug and play’ concept is designed specifically to reduce installation time by using a terminal block which can be wired during the initial installation cabling with a link (P102) to provide continuity for testing. During the commissioning phase, the links are removed and the terminal block is simply inserted
into the connector at the back of the unit. No re-termination is required.

Both break glass, supplied, and re-settable operating elements (PS230) can be used in the standard unit. Operation of the re-settable element, as well as being indicated by the units LED, is also indicated by a yellow strip on the element which becomes visible when activated. With the addition of a hinged transparent
cover (PS200) the element may be protected against accidental operation and may be further protected by using a cover seal (PS056) which requires breaking in order to operate the unit.

The call point uses one of 99 possible addresses which is simply ‘dialled in’ using the two rotary decade switches on the rear of the unit.

A specialist test key may be inserted into the bottom of the unit to lower the glass and release the micro-switch and thus a full functional test is achieved.

FEATURES
  • Unique ‘Plug & Play’ installation concept
  • Re-settable operating element option
  • Analogue addressable communications
  • Semi-Flush or surface mounting
  • Fully compliant with EN54, Part 11
  • Backward compatibility
  • Enhanced aesthetics
  • Integral LED
  • Integral loop isolation option

MI/DCZRM
MI/DCZRM
PCONVENTIONAL ZONE MODULE, MIAS, IN
MI/DCZRM

The MI-DCZRM addressable zone monitor module allows a zone of non-addressable devices to communicate with a Morley-IAS protocol analogue addressable system. As a result existing non-addressable zones can be integrated into a Morley-IAS protocol system.

The module monitors a zone of two-wire non-addressable devices. Each MI-DCZRM uses one of 99 available module addresses on a loop. A fault signal will be transmitted to the panel in case of an open circuit or short circuit on the non-addressable zone wiring or when the external fault input is pulled low (can be used for power supply monitoring). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations).

The non-addressable zone can be powered from the analogue communication loop or from an external power supply. Where the non-addressable zone is powered from an external power supply, the communication loop is fully isolated from the non-addressable zone and from the power
supply.

The zone monitor module replaces the MI-CZME but can be mounted onto a DIN rail. It can also be powered from the addressable loop and allows integration of non-addressable zones into an addressble system. This module enables non-addressable devices to be monitored by Morley-IAS protocol analogue addressable fire alarm control panels.

The maximum recommended number of non-addressable devices that can be used with the MI-DCZRM is 20

FEATURES
  • Connection of a zone of non-addressable detectors to an analogue addressable fire system
  • Built in isolation allowing system installation in stages without loss of protection
  • Monitors open circuit and short circuit faults
  • TRI-Colour Status LED
  • Zone powered from addressable loop wiring or external 24V PSU
  • Remote reset of non-addressable zone
  • Compatible with:
    • Most non-addressable detectors
    • IS non-addressable detectors
  • Monitoring of external power supply
  • External fault input
  • CPD approval to EN54-17 and EN54-18, LPCB and VdS
  • DIN rail mountable, consistent with all other modules
  • Support for an extended power supply range as low as 18Vdc 60mA with an External PSU

MI/DISO
MI/DISO
ISOLATOR MODULE, MIAS, IN
MI/DISO

The Morley-IAS loop isolator module is used on the Morley-IAS intelligent fire alarm control panels to
protect the system against wire-to-wire short circuits on the analogue addressable loop wiring.

The fault isolator modules should be placed between groups of sensors on the loop wiring to protect the loop if a short circuit fault occurs. If a short circuit fault occurs, the two isolators located either side of the short circuit fault will automatically sense the voltage drop, open their switches and remove the devices from the rest of the loop. If the line voltage then rises above a fixed threshold, indicating that the short circuit fault is removed, then the isolator module will automatically restore the power to the isolated group of devices.

The MI-DISO isolator uses a unique mechanical design allowing each module to be mounted either in a wall box or on a DIN rail. Irrespective of the mounting method chosen, the address switch is both visible and accessible for selection. To help engineers in the maintenance and fault finding process, both the LEDs and the address switches can be viewed without having to remove the cover of the mounting box. The LEDs, being multi colour, provide diagnostic information regarding the status of the isolator.

FEATURES
  • DIN rail mounting option
  • Surface mounting option
  • Plug in connectors
  • Tri-colour LED status indication
  • Address selector switches visible in 2 planes
  • LED status visible in 2 planes
  • Approved to GEA GEI 1-082 and CEA GEI 1-084

MI/DMM2I
MI/DMM2I
PINPUT MODULE DUAL, MIAS, IN
INPUT MODULE SINGLE, MIAS, IN
MI/DMMI /MI-DMM2I

The MI-DMMI and MI-DMM2I monitor modules are used with the Morley-IAS intelligent fire alarm control panels to provide a single or dual input circuit from external devices.

Each input is continuously monitored for normal, open circuit and alarm conditions. Changes to the status of
the input circuits are communicated to the panel where the appropriate actions may be undertaken.

The MI-DMMI requires a single address and the MI-DMM2I two addresses of the ninety-nine possible module addresses available on a loop. It responds to regular polling from the control panel indicated by a pulsing LED every successful communication.

The MI-DMMI and MI-DMM2I use a unique mechanical design allowing each module to be mounted either in a wall box (M200E-SMB) or on a DIN rail (using M200E-DIN). Irrespective of the mounting method chosen, the address switch is both visible and accessible for selection. To help engineers in the maintenance and fault finding process, both the LEDs and the address switches can be viewed without having to remove the
cover of the mounting box. The LEDs, being multi colour, provide diagnostic information regarding
the status of the output. For ease of installation, testing and maintenance, the field wiring terminals are of a plug in design

FEATURES
  • Single or dual inputs
  • DIN rail mounting option
  • Surface mounting option
  • Tri-colour LED status indication
  • Built-in short circuit isolators
  • Visible address selector switches
  • LED status visible in 2 planes
  • Plug in connectors
  • Approved to GEA GEI 1-082 and CEA GEI 1-084

MI/D2ICMO
MI/D2ICMO
2 INPUT, 1 OUTPUT MODULE, MIAS, IN
MI/D2ICMO

The MI-D2ICMO dual input/single output modules are used with the Morley-IAS intelligent fire alarm control
panels to provide a dual input circuit from external devices and a single relay control output circuit.

Each input is continuously monitored for normal, open circuit and alarm conditions. Any change in the status of the input circuits are communicated to the panel where the appropriate actions may be undertaken. A single pole volt free changeover relay is available for control of external devices or circuits.

The MI-D2ICMO requires three addresses per unit of the ninety-nine possible module addresses available on a loop. It responds to regular polling from the control panel indicated by a pulsing LED every successful communication.

The MI-D2ICMO uses a unique mechanical design allowing each module to be mounted either in a wall box (M200E-SMB) or on a DIN rail (using M200E-DIN). Irrespective of the mounting method chosen, the address switch is both visible and accessible for selection. To help engineers in the maintenance and fault finding process, both the LEDs and the address switches can be viewed without having to remove the cover of the
mounting box. The LEDs, being multi colour, provide diagnostic information regarding the status of the output. For ease of installation, testing and maintenance, the field wiring terminals are of a plug in design.

FEATURES
  • Dual inputs
  • Single relay output
  • DIN rail mounting option
  • Surface mounting option
  • Tri-colour LED status indication
  • Built-in short circuit isolators
  • Visible address selector switches
  • LED status visible in 2 planes
  • Plug in connectors
  • Approved to GEA GEI 1-082 and CEA GEI 1-084

MI/DCMO
MI/DCMO
OUTPUT MODULE, MIAS, IN
MI/DCMO

The Morley-IAS MI-DCMO control output module is used with the ZX series of intelligent conrol panels to provide either a single alarm circuit or Form C relay.

The MI-DCMO can be used to operte dry contacts for door holders, air handling unit shut down or other
similar functions. Optionally the module can be used to supervise wiring to the ouput load providing monitoring of the external load voltage or power supply. If the monitored voltage falls below threshold then a fault condition will be indicated.

Each MI-DCMO uses one of the ninety-nine possible module addresses available on a loop. It responds to
regular polling from the conrtol panel indicated by a pulsing LED every successful communication. On
command from the control panel the MI-DCMO will disconnect the supervision and connnect the external
power supply across the load. The disconnection of the supervision provides a positive indication to the control panel that the relay is activated. The MI-DCMO has a built-in isolator which may be switched out if required.

FEATURES
  • DIN rail mounting option
  • Surface mounting option
  • Tri-colour LED status indication
  • Built-in Short Circuit Isolators
  • Visible Address selector switches
  • LED status visible in 2 planes
  • Plug in connectors
  • Approved to GEA GEI 1-082 and CEA GEI 1-084

MI/D240CMO
MI/D240CMO
OUTPUT MODULE 240V, MIAS, IN
MI/D240CMO /MI-D240CMO-DIN

The Morley-IAS MI-D240CMO and MI-D240CMO-DIN control output modules are used with the Morley-IAS
intelligent fire alarm control panels to provide management of 240Vac loads.

The modules are loop powered devices controlling an unsupervised double pole relay output with one
normally open and one normally closed contact. The output relay is a bistable device, latching in either the on or the off state on command from the fire alarm control panel.

Each module uses one of the ninety-nine possible module addresses available on a loop. It responds to
regular polling from the control panel, indicated by a pulsing LED every successful communication. Each
module is supplied with a built-in isolator for protection. However, to increase application flexibility individual isolators may be switched out as required.

The modules are supplied in two individual mounting styles. The MI-D240CMO is supplied in a wall mounting enclosure complete with a grounding terminal. The MI-D240CMO-DIN is designed to mount on to standard 35mm “tophat” style DIN rail and is required to be installed within a suitable enclosure.

To help engineers in the maintenance and fault finding process, both the LEDs and the address
switches can be viewed without having to remove the cover of the mounting box. The LEDs, being
multi colour, provide diagnostic information regarding the status of the output. For ease of installation, testing and maintenance, the field wiring terminals are of a plug in design.

FEATURES
  • 240Vac mains switching
  • DIN rail mounting option
  • Surface mounting option
  • Bi-colour LED status indication
  • Built-in Short Circuit Isolators
  • Visible Address selector switches
  • Plug in connectors
  • Approved to GEA GEI 1-082 and CEA GEI 1-084